Skip to content

Scale, misalignment and bias

The accelerometer and gyroscope model of Rehder et al., ICRA 2016, fitted with the multi-position method of Tedaldi et al., ICRA 2014.

Recording

Start at rest for intrinsics.static.init (4 s). Then hold the sensor still in at least nine orientations, twelve covering all octants if possible, and rotate about a different axis between holds. Without rotation about distinct axes only the gyroscope bias is fitted.

Guided recording

dedrunk imu record reads a live IMU from the Minot network, prompts for each orientation, detects when the sensor has settled and fits the result:

pelorus online raw imu &
dedrunk imu record /ouster/imu --bag intrinsics.mcap -O imu_intrinsics.yaml

--poses sets the number of orientations (12, at least 9). Publisher and Dedrunk must use the same --coord-mode. After Ctrl+C the recording is kept for dedrunk intrinsics imu.

Fit

dedrunk intrinsics imu calib_drive -O imu_intrinsics.yaml
poses: 12   duration: 42.5 s   rate: 200.0 Hz
accelerometer: rms 0.0021 m/s^2, max 0.0043 m/s^2
gyroscope:     rms 0.021°, max 0.055° over 11 segments

The still stretches are found automatically. An accelerometer residual of a few mm/s² is typical for MEMS parts. Larger values point to similar orientations or a soft support.

When only the six axis-aligned faces are reachable, the reduced model drops misalignment and needs six holds:

dedrunk intrinsics imu calib_drive -o intrinsics.accel_model='"scale-bias"'

Merge the result with the noise file, see results.